Specifications:
|
| CCU1 |
:
Combined Ceiling Unit |
| OccupancySensor |
: Passive Infra-Red Detector |
| field
of view |
:
360 degrees |
| coverage |
:
diameter = 2.5 x height |
| Light
Sensor |
:
Photo-Darlington |
| light
range |
:
25 - 2,000 Lux, preset by remote control |
| Remote
Control Sensor |
:
Active Infra-Red @ 33KHz, encoded |
| range
|
:
2 - 3 metres, 60 degree angle |
| Timer |
:
4,8 or16 minutes, preset by remote control |
| Supply
Voltage |
:
230V A.C. @ 50Hz |
| Relay
Switching Capacity |
:
8 Amps Inductive |
| Electrical
Connections |
:
Live, Neutral and Switched Live |
| CCU1F/VF
|
:
Combined Ceiling Unit / Volt-Free |
| as
CCU1
except Electrical Connections |
: Live, Neutral,
Common and N/O
|
| CLC1F
as CCU1 except |
: Ceiling Low Current |
|
Relay Switching Capacity |
:
2 Amps @ 30V, 100mA @ 230V AC |
| Electrical
Connections : |
:
Live, Neutral, Common and N/O |
| |
|
| Products
and Codes: |
|
| CCU1F
|
:
CCU1, Flush fitting for ceiling tiles |
| size
|
:
58mm deep x 54mm dia., face 75mm dia. |
| weight
|
:
250g |
| CCU1S |
:
CCU1, Surface fitting for hard surfaces |
| size |
:
with CUR1, 78mm deep x 61mm dia. |
| weight |
:
with CUR1, 170g |
| |
|
| Also
Available: |
|
| Kit
‘K’ |
:
Converts Flush to Klip fitting |
| ITX1,
supplied with above units |
:
Miniature I.R. remote control |
| CUR1,
supplied with CCU1S |
:
Surface mounting receptacle. |
| ITX2
|
:
Hand-Held I.R. remote control |
| THC |
:
54mm Tile Hole Cutter |
| |
|
| Specifications: |
|
| CWU1/1
|
:
Combined Wall Unit |
| Occupancy
Sensor |
:
Passive Infra-Red Detector |
| field
of view |
:
120 degrees maximum |
| coverage
|
:
12 metres maximum |
| Light
Sensor |
: Photo-Darlington |
| light
range |
:
25 - 2,000 Lux, preset by remote control |
| Remote
Control Sensor |
:
Active Infra-Red @ 33KHz, encoded |
| range
|
:
2 - 3 metres, 60 degree angle |
| Timer
|
:
4,8 or 16 minutes, preset by remote control |
| Supply
Voltage |
:
230V A.C. @ 50Hz |
| Relay
Switching Capacity |
:
8 Amps Inductive |
| Electrical
Connections |
:
Live, Neutral, Com1 and N/O1 |
| |
|
| CWU1/2 |
:
Combined Wall Unit, Dual Light Zones |
| as
CWU1/1except |
|
| Relay
Switching Capacity |
:
2 x 8 Amps Inductive |
| Electrical
Connections |
:
Live, Neutral,
Com1, N/O1, Com2 and N/O2 |
|
|
|
N.B.
N/O1 is connected to Live as supplied,
|
|
|
this
can be removed to give volt free contacts.
|
|
| |
|
| Products
and Codes |
: |
| CWU1/1 |
: CWU1/1 Single relay version. |
| size |
:
128mm x 77mm x 49mm |
| weight |
:
130g |
| CWU1/2
|
:
CWU1/2, Dual light zones, two relays |
| size |
:
128mm x 77mm x 49mm |
| weight |
:
200g |
| |
|
| Also
Available: |
|
| ITX1,
supplied with above units |
:
Miniature I.R. remote control |
| ITX2 |
:
Hand-Held I.R. remote control |
| |
|
| Specifications: |
|
| ELC1 |
:
External Light Controller |
| Light
Sensor |
:
Photo-Darlington |
| light
range |
:
10 - 2,000 Lux, preset by remote control |
| Remote
Control Sensor |
:
Active Infra-Red @ 33KHz, encoded |
| range |
:
up to 10 metres, 60 degree angle |
| Light
control delay |
:
30 seconds of continuous change |
| Supply
Voltage |
:
230V A.C. @ 50Hz |
| Output |
:
Volt-Free Normally Open Contacts |
| Electrical
Connections |
: Input Live
& Neutral (DC= + & - , AC= ~ & ~)
|
|
: Output N/O & COM |
| Case
|
:
ABS, IP65 rated |
| Size
& Weight |
:
90mm dia. x 55mm deep, max 170 gm |
| |
|
| Products
and Codes: |
|
| ELC1 |
:
ELC1 with 230V A.C. @ 50 Hz input |
| Output
contact rating |
:
10mA to 8 Amp. Inductive @ max 440V A.C.. |
| ELC1/1D
or ELC1/1A |
:
ELC1 with 12V D.C. or 12V A.C. input |
| ELC1/2D
or ELC1/2A |
:
ELC1 with 24V D.C. or 24V A.C. input |
| 12V
and 24V output contact rating |
:
10uA to 2 Amp.Resistive @ max 30V D.or A.C. |
| ITX1P,
supplied with above units |
:
Miniature I.R. remote control |
| ITX2P |
:
Hand-Held I.R. remote control |
| |
|
| Also
Available |
|
|
to Special Order: |
|
| ELC1/277 |
:
ELC1 277V A.C. @ 60 Hz input, 8 Amp output |
| ELC1/110 |
:
ELC1 110V A.C. @ 60 Hz input, 8 Amp output |
| ELC1/xx/HD1 |
:
ELC1 with 8 Amp. relay output, xx = see below |
| ELC1/xx/OC1 |
:
ELC1 Open Collector output, xx = see below |
| |
:
1xx = low voltage input code e.g. 1D |